4. WIRING
IMR01Y06-E6
12
Connection diagram
Always connect a termination resistor between the DA and DB terminals of the module to
be located at the far end.
Termination resistor: 110 Ω ± 5 % 1/2 W
CC-Link dedicated
cable Ver. 1.10
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
DA
DB
DG
SLD
FG
TR
COM-JC
Master station
COM-JC
TR
TR: Termination resistor
CC-Link dedicated
cable Ver. 1.10
The CC-Link dedicated cable Ver. 1.10 is provided by the customer.