RKC INSTRUMENT COM-JC Manual de instrucciones Pagina 28

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 106
  • Tabla de contenidos
  • SOLUCIÓN DE PROBLEMAS
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 27
6. CC-Link COMMUNICATION
IMR01Y06-E6
22
6.2 CC-Link Flag Operation
Remote input/output and Remote register flag operations are as follows.
[Example] When the Occupied station/Extended cyclic of COM-JC is set to 1 station occupied 1 time.
Initialize request processing at power on
z Initialize processing request from Remote device station (COM-JC)
If the COM-JC is initialized at power on, the Initialize data processing request flag [RX(n+1)8] is
turned on. Thus, turn on the Initialize data processing completion flag [RY(n+1)8].
When COM-JC becomes a ready state, a Remote ready [RX(n+1)B] is turned on.
Initialize data processing
request flag [RX(n+1)8]
Initialize data processing
completion flag [RY(n+1)8]]
Remote ready [RX(n+1)B]
ON
OFF
ON
OFF
ON
OFF
z Initialize processing request from Master station (PLC)
This is a COM-JC initialize setting request. As there is no initialize data specifically, no processing is
required.
Initialize data setting
request flag [RY(n+1)9]
Initialize data setting
completion flag [RX(n+1)9]
Remote ready [RX(n+1)B]
ON
OFF
ON
OFF
ON
OFF
Vista de pagina 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 ... 105 106

Comentarios a estos manuales

Sin comentarios