Features
Temperature/Process Controller FB900/400
PID control algorithm is selectable in the FB Series to achieve
the most precise control for various applications.
PV Derivative PID : suitable for fixed setpoint control (Factory
setting)
Deviation Derivative PID : suitable for ramp control using ramp-
to-setpoint function and cascade control.
Selectable sampling time makes the FB Series suitable for any
application ranging from pressure control requiring fast
response to precise control requiring highest resolution. The
selections are 100ms (factory setting) usually suitable for most
of standard applications, 50ms for fast response applications,
and 250ms for precise control requiring high-resolution. The PID
parameters can be set in 1/10 unit which supports fast and
accurate control. Ramp-to-setpoint and output-change-limiter
functions are each settable for UP and DOWN so that a special
heater can be controlled precisely.
Advanced Heat/Cool PID algorithm achieves stable control by
the Undershoot Suppression (USS) function, and independent
P-I-D settings for both Heat and Cool which are effective for
applications with strong cooling gain. Control Response type
selection is settable to avoid overshoot at start-up and against
external disturbance. The FB Series also offers selection of
water cool and air cool PID control algorithm.
The control type is configurable among Heat, Cool, Heat/Cool,
and position proportioning.
Brilliant II PID Control
SV
SV
PV
PV
200
SV PV
100
200
SV PV
100
SV
SV
FAST
MEDIUM
SLOW
PV
SV SV
PV PV
PV derivative type PID control
Deviation derivative type PID control
Overshoot
Hunting
Most adaptive to conventional
fixed value control
Follow-up
Follow-up
Most adaptive to
conventional
fixed value control
250ms sampling controller
50ms sampling controller
1 sec 1 sec
(˚C) (˚C)
Control response parameter
USS (Under Shoot Suppression) gain
USS gain : Small
USS gain : Large
* USS setting range : 0.000 to 1.000
Only execution at
power ON
Only execution at
SV change
Execution at power ON and
SV change
AT function when limiter is effective.
AT function when limiter is not effective.
Tuning
ON
Tuning
ON
Tuning
ON
Tuning
ON
SV
Power ON
SV2
SV1
SV2
SV1
SV change
Power ON
SV change
AT output limiter
High
AT output limiter
Low
Output 100%
Output 0%
Output 100%
Output 0%
AT ON AT ON
Selectable PID control algorithm
The improved Autotuning alrogithm calculates optimum PID
parameters. For Heat/Cool control, PID parameters for both
sides (Heat and Cool) are calculated.
Autotuning
Autotuning to calculate optimum PID parameters
Output limiters high and low for autotuning enables autotuning
to be used with any application in which the output has to be
within limited range, even during autotuning. High and low are
independently settable.
Output limiters high and low for autotuning
Start-up tuning eliminates time required for conventional
autotuning as it calculates optimum PID values by temperature
characteristics at start up. It is useful in applications which
require a long time for conventional autotuning. The timing of
activation of start-up tuning can be selected from at power-up,
at setpoint change, and at power-up/setpoint change. It is also
settable to Only-once or always-ON.
Start-up tuning to eliminate time for autotuning
Selectable sampling time among 50ms, 100ms, and 250ms.
Advanced Heat/Cool PID algorithm with Undershoot
Suppression
Configurable control type
• Startup tuning is not available with Heat/Cool PID control type.
• Validity/invalidity of the startup tuning function can be set.
• Heater power needs to be turned on simultaneously with or before turning on power
to the temperature controller.
• If start-up tuning does not calculate suitable PID values due to characteristics of
application, use Autotuning function.
3FB_01E