Input
Main Output
Control
Input
Universal input
a) Temperature, Current, Low voltage input group
Thermocouple : K, J, R, S, B, E, T, N (JIS/IEC), PLII (NBS),
W5Re/W26Re (ASTM), U, L (DIN)
•Influence of external resistance : Approx. 0.2µV/Ω
•Input break action : Up-scale / Down-scale (Selectable)
RTD : Pt100 (JIS/IEC), JPt100 (JIS)
•Influence of input lead resistance : Approx. 0.01[%/Ω] of reading
•Maximum 10Ω per wire
•Input break action : Up-scale
Low voltage : 0 to 1V DC, 0 to 100mV DC, 0 to 10mV DC,
-100 to +100mV DC, -10 to +10mV DC
•Input break action : Up-scale / Down-scale (Selectable)
Current : 4 to 20mA DC, 0 to 20mA DC
•Input break action : Uncertain (indicates a value around 0mA)
b) High voltage input group
High voltage : 0 to 5V DC, 1 to 5V DC, 0 to 10V DC, -1 to +1V DC
•Input break action : Uncertain (indicates a value around 0V)
Sampling Time
0.1 sec
• 0.05sec or 0.25sec is available.
Input Digital Filter
0.1 to 100.0 sec (OFF when 0 is set.)
PV Bias
-
span to +span
PV Ratio
0.500 to 1.500
Square Root Extraction
Equation : PV = √ (Input value x PV ratio + PV bias)
Low level cut OFF : 0.00 to 25.00% of span
Control Method
a) Brilliant II PID control
•Available for reverse and direct action.
b) Brilliant PID control (Heat/Cool type)
c) Position proportioning control without feedback resistance.
•a), b), c) is selectable.
Autotuning Method
a) For PID control (Direct action/Reverse action)
b) For Heat/Cool PID control (For extruder, air cooling type)
c) For Heat/Cool PID control (For extruder, water cooling type)
d) For Heat/Cool PID control
Startup tuning
The condition to activate Startup Tuning is selectable among a) to g)
a) At power-on, one-time tuning
b) At SV change, one-time tuning
c) At power-on and SV change, one-time tuning
d) At power-on, always on
e) At SV change, always on
f) At power-on and SV change, always on
g) Function off
(Not available for Heat/Cool PID control type)
Major Setting Range
Set value : Same as input range.
Proportional band
:
0 to input span (Temperature input)
0.0 to 1000.0% of span (Voltage, Current input)
(ON/OFF control when P = 0)
Integral time : 0 to 3600sec. or 0.0 to 1999.9sec.
(selectable)
Derivative time : 0 to 3600sec. or 0.0 to 1999.9sec.
(selectable)
Cool-side proportional band
: 1
to input span (Temperature input)
0.1 to 1000.0% of span (Voltage, Current input)
Cool-side integral time
: 0 to 3600sec. or 0.0 to 1999.9sec.
(selectable)
Cool-side derivative time
: 0 to 3600sec. or 0.0 to 1999.9sec.
(selectable)
Deadband/Overlap : -span to +span (Temperature input)
-100.0 to +100.0% of span (Voltage, Current input)
Control response : Slow, Medium, Fast
Ramp-to-setpoint :
0 to span per Time
(Time is selectable between 1 and 3600 sec)
(Up/Down individual setting)
Output limiter : -5.0 to +105.0%
(High/Low individual setting)
Cool-side output limiter : -5.0 to +105.0%
(High/Low individual setting)
Output change rate limiter :
0.0 to 100.0%/sec. (Up/Down individual setting)
Cool-side o
utput change rate limiter
:
0.0 to 100.0%/sec. (Up/Down individual setting)
Proportional cycle time : 0.1 to 100.0 sec.
Cool-side proportional cycle time :
0.1 to 100.0 sec.
Manual reset : -100.0 to +100.0%
Output at control stop mode :
-5.0 to 100.5%
(Heat/Cool individual setting)
Motor Valve Control (position proportioning control type only)
Motor time : 5 to 1000 sec. (full open to full close)
Integral output limiter :
OFF, 100.0 to 200.0% of motor time
Neutral zone : 0.1 to 10.0%
Differential gap : 0.1 to 5.0%
Valve action at a stop mode
: a) CLOSE : OFF, OPEN : OFF
b) CLOSE : ON, OPEN : OFF
c) CLOSE : OFF, OPEN : ON
• a), b), c) is selectable.
Memory area
Number of memory area : 8 memory areas
Setting item :
Set value (SV), Proportional band, Integral time,
Derivative time, Cool-side proportional band,
Cool-side integral time,
Cool-side derivative time,
Deadband/Overlap, Control response,
Manual reset,Ramp-to-setpoint (Up/Down),
Event set vale, LBA time, LBA deadband,
Soak time : 0 min 0.00 sec to 199 min 59 sec or
0 hr 00 min to 9 hr 59 min
(selectable)
Linking area number : OFF, 1 to 8
Number of Main Output
Up to 2 points (OUT1, OUT2)
Output Items
Control output, HBA output, FAIL output
Output Type
Relay output :
Form A contact, 250V AC 3A (resistive load)
Voltage pulse output : 0/12V DC
(Load resistance : More than 600Ω)
Current output :
4 to 20mA DC, 0 to 20mA DC
(Load resistance : Less than 600Ω)
Continuous voltage output
:
0 to 1V DC, 0 to 5V DC, 1 to 5V DC, 0 to 10V DC
(Load resistance : More than 1kΩ)
SSR (Triac) output : Rated current : 0.5A
Open collector output : Load voltage : Less than 30V DC,
(Sink type) Maximum load current : Less than 100mA
ON voltage : Less than 2V DC (at 100mA)
Performance
Measuring Accuracy
a) Thermocouple
Type : K, J, T, E, N, PLII, U, L
Less than -100˚C (-148˚F) : ±1.0˚C (±1.8˚F)
-100 to 500˚C (-148 to 932˚F) : ±0.5˚C (±0.9˚F)
More than 500˚C (932˚F) : ±(0.1% of Reading + 1 digit)
Type : N, S, R, W5Re/W26Re
Less than 0˚C (32˚F) : ±2.0˚C (±3.6˚F)
0 to 1000˚C (-148 to 1832˚F) : ±1.0˚C (±1.8˚F)
More than 1000˚C (1832˚F) : ±(0.1% of Reading + 1 digit)
Type : B
Less than 400˚C (752˚F) : ±70.0˚C (±126˚F)
400 to 1000˚C (752 to 1832˚F) : ±1.4˚C (±2.5˚F)
More than 1000˚C (1832˚F) : ±(0.1% of Reading + 1 digit)
Cold junction temperature compensation error
±1.0˚C (1.8˚F) [at 5 to 40˚C (41 to 104˚F)]
Within ±1.5˚C (± 2.7˚F)
[Between -10 and 5˚C (14 to 41˚F), 40 and 50˚C (104 to 122˚F)]
b) RTD
Less than 200˚C (392˚F) : ±0.2˚C (±0.4˚F)
More than 200˚C (392˚F) : ±(0.1% of Reading + 1 digit)
c) DC voltage and DC current
±(0.1% of span)
•Close horizontal mounting error : ±1.5˚C (±2.7˚F)
Insulation Resistance
More than 20MΩ (500V DC) between measured terminals and ground
More than 20MΩ (500V DC) between power terminals and ground
Dielectric Strength
1000V AC for one minute between measured terminals and ground
Specifications
Temperature/Process Controller FB900/400
6 FB_01E